6. Alarm Activation
6-4 External output operation
103 / 168
CAUTION
<With analog transmission (4 - 20 mA)>
The 4 - 20 mA output is already adjusted. If the full scale is exceeded, the output will not exceed 20.5 mA.
If the inhibit function is enabled or initialization is underway, the output follows the 4 - 20 mA output setting
in maintenance mode. Note that the output may become low (e.g., 2.5 mA during initialization) when
using ESF (detection target gas: oxygen). Special care is required when starting the product or after
altering specifications.
Make sure you fully understand the operation details and take appropriate precautions where necessary
(e.g., setting to skip state) to prevent false alarms on the receiving side.
Particular care is required in the following situations:
Examples where care is required
Analog transmission
4 - 20 mA specifications
Using ESF (detection target gas: oxygen)
(L-LL, L-H)
A false alarm may occur upstream (L alarm) if
2.5 mA is output in maintenance mode or if the
inhibit function is enabled.
Changed to ESF specifications
(detection target gas: oxygen 0 - 25 vol%)
If changed from another principle (H-HH), 4 mA
(equivalent to zero concentration) is output until the
change is confirmed (until [C-02] is displayed).
Changed from ESF specifications
(detection target gas: oxygen 0 - 25 vol%)
If changed from 0 to 25 vol% (L-LL, L-H), 17.4 mA
(equivalent to approximately 84 %FS) is output until
the change is confirmed (until [C-02] is displayed).
Summary of Contents for GD-3EC
Page 169: ...11 Appendix Revision History 169 168...
Page 170: ...11 Appendix Revision History 170 168...
Page 171: ...11 Appendix Revision History 171 168...
Page 172: ...11 Appendix Revision History 172 168...
Page 173: ...11 Appendix Revision History 173 168...
Page 174: ...11 Appendix Revision History 174 168...
Page 175: ...11 Appendix Revision History 175 168...