104
6.5.14 Real number to ASCII code
Input/output Operand
Data type
IN
VD, ID, QD, MD, SD, SMD, LD, AC, constant, *VD, *LD, *AC
Real number
FMT
VB, IB, QB, MB, SB, SMB, LB, AC, constant, *VD, *LD, *AC
Byte
OUT
VB, IB, QB, MB, SB, SMB, LB, *VD, *LD, *AC
Byte
RTA:The instruction converts the real number to ASCII
characters. (FMT) format specifies the conversion
accuracy of the right of the decimal point.
The conversion result is placed in the output buffer from
the OUT.The length of the output buffer is 3 to 15
characters.
Error conditions:
nnn > 5
ssss < 3
ssss <
Number of characters in OUT
The following is the RTA instruction format (FMT) operand definition:
The length of the output string is specified by the SSSS field.0, 1, or 2 bytes are not
valid.The effective range of the NNN is from 0 to 5.NNN is equal to 0, the output
shows no decimal point.When the NNN value is greater than 5 or when the specified
output string length is too small to store the conversion value, the output string is
filled with ASCII space characters.The C bit specifies using a comma (C = 1) or a
decimal point (C = 0).
The output according to the following rules:
1.Positive number is written to output buffer without a sign.
2.Negative number is written to the output buffer with
“
-
”
.
3.The starting zero on the left of the decimal point is compressed.
4. The number of characters of the right of the decimal point is equal to the value of
“
nnn
”
.
Summary of Contents for PR-12 Series
Page 26: ...19 1 xLogic CPU PR 12 Series CPU PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension...
Page 27: ...20 PR 24 series...
Page 47: ...40 5 3 Instruction tree...
Page 58: ...51 5 3 10 Instructions Instructions will be explained in detail in the instructions section...
Page 93: ...86 2 Enter the illegal real number Example...
Page 127: ...120 Example...
Page 139: ...132 Special memory bit SM1 0 Zero result SM1 1 overflow SM1 2 Negative result Example...
Page 149: ...142 Example...
Page 152: ...145 Example ATCH instruction only needs to be connected once...
Page 154: ...147 Example...
Page 175: ...168...
Page 217: ...210 Example Four arithmetic operation Main program...
Page 218: ...211 Subroutine...
Page 252: ...245 10 8 Example of serial port free port communication Program 1...
Page 254: ...247 10 9 Example of CAN free port...
Page 258: ...251 Conversion of Process quantity and set value unit...