219
8.Assignment and function of SM special storage area
SMB0
Always_On
SM0.0
Always ON
First_Scan_On
SM0.1
ON for the first scan cycle only
Clock_60s
SM0.4
30 seconds OFF,30 seconds ON
Clock_1s
SM0.5
0.5 second OFF,0.5 second ON
SMB1
Result_0
SM1.0
Set to 1 by the execution of certain instructions when
the operation result = 0
Overflow_Illegal
SM1.1
Set to 1 by exec. of certain instructions on overflow
or illegal numeric value.
Neg_Result
SM1.2
Set to 1 when a math operation produces a negative
result
Divide_By_0
SM1.3
Set to 1 when an attempt is made to divide by zero
Table_Overflow
SM1.4
Set to 1 when the Add to Table instruction attempts
to overfill the table
Table_Empty
SM1.5
Set to 1 when a LIFO or FIFO instruction attempts to
read from an empty table
Not_BCD
SM1.6
Set to 1 when an attempt is made to convert a non-BCD
value to a binary value
Not_Hex
SM1.7
Set to 1 when an ASCII value cannot be converted to
a valid hexadecimal value
The PLC variables addresses of LCD keys:
F1
→
SM191.0
F2
→
SM191.1
F3
→
SM191.2
F4
→
SM191.3
ESC
→
SM190.0
OK
→
SM190.1
UP
→
SM190.2
DOWN
→
SM190.3
LEFT
→
SM190.4
RIGHT
→
SM190.5
When the value of SM192.0 is equal to 1,LCD will be bright.
When the value of SM192.0 is equal to 0,LCD will be dark.
SMW22-SMW26
Scan time
SMW22
Scan time of the last scan.
SMW24
Minimum scan time
SMW26
Maximum scan time
Summary of Contents for PR-12 Series
Page 26: ...19 1 xLogic CPU PR 12 Series CPU PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension...
Page 27: ...20 PR 24 series...
Page 47: ...40 5 3 Instruction tree...
Page 58: ...51 5 3 10 Instructions Instructions will be explained in detail in the instructions section...
Page 93: ...86 2 Enter the illegal real number Example...
Page 127: ...120 Example...
Page 139: ...132 Special memory bit SM1 0 Zero result SM1 1 overflow SM1 2 Negative result Example...
Page 149: ...142 Example...
Page 152: ...145 Example ATCH instruction only needs to be connected once...
Page 154: ...147 Example...
Page 175: ...168...
Page 217: ...210 Example Four arithmetic operation Main program...
Page 218: ...211 Subroutine...
Page 252: ...245 10 8 Example of serial port free port communication Program 1...
Page 254: ...247 10 9 Example of CAN free port...
Page 258: ...251 Conversion of Process quantity and set value unit...