207
6.18.2 Using parameters to call subroutine
Subroutine may contain the transfer parameters.The parameter is defined in the local
variable table of the subroutine.Parameters must have a symbol name (up to 23
characters), a variable type, and a data type.Each subroutine can be set up to 16
IN/OUT parameters.
Local variable table has 4 types of variables.They are IN, IN-OUT, OUT and TEMP.
Parameter type and description
IN
Parameters are transferred to the subroutine.If the parameter is a
direct address (e.g. VB10),the specified location value is transferred to the
subroutine.If the parameter is an indirect address (such as *AC1),the specified
location value is transferred to the subroutine.If the parameter is the data constant
(16#1234) or address (&VB100)
,
constants or addresses are transferred to the
subroutine.
IN_OUT
The specified location value is transferred to the subroutine.The
result of subroutine operation is transferred to the specified same location .This
parameter does not allow to use constants (such as 16#1234) and addresses
(e.g.&VB100).
OUT
The result of subroutine operation is transferred to the specified
location.Constants (such as 16#1234) and addresses (e.g. &VB100) are not allowed to
be used as output.
TEMP
Any local memory which is not used as a transfer parameter can
’
t be
used for temporary storage in subroutine.
Parameter data type
Illustration
Boolean
It is used for unit input and output.
Byte, word, double word
Input or output parameters without symbols.
Summary of Contents for PR-12 Series
Page 26: ...19 1 xLogic CPU PR 12 Series CPU PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension...
Page 27: ...20 PR 24 series...
Page 47: ...40 5 3 Instruction tree...
Page 58: ...51 5 3 10 Instructions Instructions will be explained in detail in the instructions section...
Page 93: ...86 2 Enter the illegal real number Example...
Page 127: ...120 Example...
Page 139: ...132 Special memory bit SM1 0 Zero result SM1 1 overflow SM1 2 Negative result Example...
Page 149: ...142 Example...
Page 152: ...145 Example ATCH instruction only needs to be connected once...
Page 154: ...147 Example...
Page 175: ...168...
Page 217: ...210 Example Four arithmetic operation Main program...
Page 218: ...211 Subroutine...
Page 252: ...245 10 8 Example of serial port free port communication Program 1...
Page 254: ...247 10 9 Example of CAN free port...
Page 258: ...251 Conversion of Process quantity and set value unit...