4.1 Special memory area:
SMB0
Always_On
SM0.0
Always ON
First_Scan_On
SM0.1
ON for the first scan cycle only
SMB1
Result_0
SM1.0
Set to 1 by the execution of certain instructions when
the operation result = 0
Overflow_Illegal
SM1.1
Set to 1 by exec. of certain instructions on overflow
or illegal numeric value.
Neg_Result
SM1.2
Set to 1 when a math operation produces a negative
result
Divide_By_0
SM1.3
Set to 1 when an attempt is made to divide by zero
Table_Overflow
SM1.4
Set to 1 when the Add to Table instruction attempts
to overfill the table
Table_Empty
SM1.5
Set to 1 when a LIFO or FIFO instruction attempts to
read from an empty table
Not_BCD
SM1.6
Set to 1 when an attempt is made to convert a non-BCD
value to a binary value
Not_Hex
SM1.7
Set to 1 when an ASCII value cannot be converted to
a valid hexadecimal value
4.2Interrupt Events:
I1.2 Rising edge
PLC_EVENT_INPUTP0
0
Highest priority
I1.4 Rising edge
PLC_EVENT_INPUTP1
1
High priority
Timer interrupt 0
PLC_EVENT_TIMER0
10
Low priority
Timer interrupt 1
PLC_EVENT_TIMER1
11
Lowest priority
4.3 High speed counter
:
PR-24DC-DA-R/PR-24DC-DAI-RTA
I1.0
HC0
I1.1
HC1
I1.2
HC2
I1.3
HC3
Each high speed counter occupies an input point for receiving the pulse.No
reset, adjust the direction, start and other functions.The high speed
counter can only be used for recording number in the PLC.The number of
Summary of Contents for PR-12 Series
Page 26: ...19 1 xLogic CPU PR 12 Series CPU PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension...
Page 27: ...20 PR 24 series...
Page 47: ...40 5 3 Instruction tree...
Page 58: ...51 5 3 10 Instructions Instructions will be explained in detail in the instructions section...
Page 93: ...86 2 Enter the illegal real number Example...
Page 127: ...120 Example...
Page 139: ...132 Special memory bit SM1 0 Zero result SM1 1 overflow SM1 2 Negative result Example...
Page 149: ...142 Example...
Page 152: ...145 Example ATCH instruction only needs to be connected once...
Page 154: ...147 Example...
Page 175: ...168...
Page 217: ...210 Example Four arithmetic operation Main program...
Page 218: ...211 Subroutine...
Page 252: ...245 10 8 Example of serial port free port communication Program 1...
Page 254: ...247 10 9 Example of CAN free port...
Page 258: ...251 Conversion of Process quantity and set value unit...