If the updated value PV > SP, then the special function reduces the value of AQ.
If the updated value PV < SP, then the special function increases the value of
AQ.
Dir = downwards/- (timing diagram number 2)
If the updated value PV > SP, then the special function increases the value of
AQ.
If the updated value PV < SP, then the special function reduces the value of AQ.
With a disturbance, AQ continues to increase / decrease until the updated value PV
again corresponds to SP. The speed with which AQ changes depends on the
parameters KC and TI. If the input PV exceeds the parameter Max., then the updated
value PV is set to the value of Max.. If the PV falls short of the parameter Min., then
the updated value PV is set to the value of Min.
If the input R is set to 1, then the AQ output is reset. As long as R is set, the input A/M
is disabled.
Sampling Time
The sampling time is fixed at 500 ms.
Parameter sets
In order to simplify the use of the PI controller, the parameters for KC, TI and Dir are
already given as sets for the following applications:
Parameter set
Application example
Parameter KC Parameter TI
(s)
Parameter
Dir
Temperature fast
Temperature, cooling control of
small spaces; small volumes
0,5
30
+
Temperature slow
Heating, ventilation, temperature,
cooling control of large spaces;
large volumes
1,0
120
+
Pressure 1
Quick
pressure
change,
compressor control
3,0
5
+
Pressure 2
Slow pressure change, differential
pressure control (flow controller)
1,2
12
+
Full level 1
Vat and/or reservoir filling without
drain
1,0
1
+
Full level 2
Vat and/or reservoir filling with
drain
0,7
20
+
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...