145
settings must be same for Q3&Q4 of ELC-12 CPU and Q5&Q6 of ELC-22/26 and upgraded ELC-18 CPUs.
5.5.29 Analog Ramp
Fashion:
Classic:
Short Description:
The Analog Ramp instruction allows the output to be changed from the current level to a selected level at
a specified rate.
Connection
Description
Input
En
A change in the status from 0 to 1 at input EN (Enable) applies the start/stop level (Offset "B"
+ StSp) to the output for 100 ms and starts the ramp operation to the selected level.
A change in the status from 1 to 0 immediately sets the current level to Offset "B", which
makes output AQ equal to 0.
Input
Sel
SeI = 0: The step 1 (level 1) is selected.
SeI = 1: The step 2 (level 2) is selected.
A change in status of Sel causes the current level to start changing to the selected level at the
specified rate.
Input
St
A change in the status from 0 to 1 at input St (Decelerated Stop) causes the current level to
decrease at a constant rate until the start/stop level (Offset "B" + StSp) is reached. The
start/stop level is maintained for 100 ms and then the current level is set to Offset "B", which
makes output AQ equal to 0.
parameter
Level1 and Level2: Levels to be reached; value range for each level: -10,000 to +20,000
MaxL: Maximum value that must not be exceeded.
Value range: -10,000 to +20,000
StSp: Start/Stop offset: value that is added to Offset "B" to create the start/stop level. If the
Start/Stop offset is 0, then the start/stop level is Offset "B").
Value range: 0 to +20,000
Rate: Speed with which level 1, level 2 or 0ffset is reached. Steps/seconds are issued.
Value range: 1 to 10,000
A: Gain
Value range: 0 to 10,00
B: Offset
Value range: +- 10.000
p: Number of decimal places
Value range: 0, 1, 2, 3
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...