197
Output AQ
AQ outputs the average value over the specified time of sampling.
* Analog Inputs: 0 to 10 V corresponds with 0 to 1000 (internal value).
Parameter St and Sn
Parameter St represents the sampling time and parameter Sn represents the number of samples.
Timing diagram
Description of the function
When En = 1, the average value function calculates the average value of the samples during the
configured time interval. At the end of the sampling time, this function sets output AQ to this calculated
average value.
When En = 0, the calculation stops, and AQ retains the last calculated value. When R = 0, AQ is reset to
0.
5.5.45 Device Reset
Fashion:
Classic:
Short description
This function block is used to reset the device (Ethernet modem or WIFI modem built-in) in the CPU, if
there is a trigger at the Trg pin. It merely can be applied to the CPU with Ethernet module or Wifi module
built-in.
Available in below CPUs:
ELC series type:
ELC-12DC-DA-R-N
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...