370
frequency
Sensor type
Contact or 3-wire PNP
Contact or 3-wire PNP
Isolation between power
supply and inputs
None
Resistive
Isolation between inputs
None
None
Protection against polarity
inversions
Yes
None
Inputs used as analog inputs
( I1-I4 )
Measurement range
---
DC 0---10V
Input impedance
---
Min, 24KΩ ; Max. 72KΩ
Input voltage
---
28.8 V DC max
Resolution
---
9bit ,0.015V
Accuracy at 25 °C
---
± (Max.0.02)V
Accuracy at 55 °C
---
± (Max.0.04)V
Isolation between analog
channel and power supply
---
None
Cable length
---
10 m max. shielded and twisted
Output parameters:
Output No.
4 (Q1-Q4)
Output type
Relay output
Continuous current
Resistive load 10A/Inductive load 2A
Max. breaking voltage
AC 250 V
/DC 110 V
Max. Allowable Power Force
1250VA
/300W
Electrical durability
Expectancy
10
5
Operations at Rated Resistive Load
Mechanical life
10
7
Operations at No Load condition
Response time
Operate Time : 15 mSec. Max.
Release Time : 10 mSec. Max.
Built-in protections
Against short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism
10Hz
Resistor/light load
2Hz
Sensitive load
0.5Hz
Other parameters:
Function blocks
64 blocks
RTC accuracy :
MAX ±2S/day
RTC Backup at 25 °C
20 days
Program and settings
Backup
10 Years
Data Power-off retentivity
No
Weight
Approx.300g
Short-circuit protection
External fuse required
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...