On initialization, PILOT OUTPUT NUMBER has the value 1. On initialization, if the tank is in the state
indicated and if a sensor above the water is in the ON state, when the user program is executed, the
INPUT 1 and INPUT 2 inputs are ON, INPUT 3 and INPUT 4 are OFF and OUTPUT 2 and OUTPUT3 are ON.
Assuming that the tank is full, INPUT 2 changes to OFF and OUTPUT 1 changes to OFF. PILOT OUTPUT
NUMBER indicates the value 2.
Assuming that the tank is empty, INPUT 2 changes back to ON, OUTPUT 3 changes to ON and OUTPUT 2
remains ON.
Assuming that the tank refills, INPUT 2 changes back to OFF, OUTPUT 2 changes to OFF and PILOT
OUTPUT NUMBER indicates the value 3.
Assuming that the tank continues to refill, INPUT 1 changes to OFF, OUTPUT 3 changes to OFF and PILOT
OUTPUT NUMBER indicates the value 4.
5.5.51 Defrost
Fashion:
Classic:
short Description
The defrost output changes to ON when the input temperature is less than the minimum temperature for
a time T (T being the cumulative duration of passages below the minimum temperature). If the
temperature rises to higher than the maximum temperature during the defrost cycle, the defrost output
reverts to OFF even if it has not finished. This output can be triggered and stopped by means of the
corresponding inputs.
Connection
Description
Input
VALIDATION
function validation input. The function remains inactive for as long as this input is not
activated. VALIDATION is implicitly active if it is not connected.
Input
TEMPERATURE
Air temperature in °C*100 (-32768°C to 32767°C).
Input
MANUAL
DEFROST ON
Sets the defrost output to ON if the temperature is less than the maximum
temperature.
Input
MANUAL
DEFROST OFF
Sets the defrost output to OFF (Priority stop).
Output
DEFROST
The defrost output is at ON when the CUMULATIVE OPERATING TIME has elapsed.
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...