161
For the detail information about I, AI, Q, AQ, registers address of xLogic ,refer to the RTU protocol file.
5.5.34 Modbus read write
Short description:
This function block is developed for the new Ethernet PLC which has web server built-in, if you need use
the Ethernet as master PLC, so block should be applied into the program.
For the CPU with "-N" type, the hardware version number is 1(built-in webserver type). If your CPU
hardware version is not 1 and without webserver built-in, you can still use the modbus read and modbus
write block to establish the communication.
You can get the hardware version number by Tools-> transfer-> get PLC version number.
When a high level in En, the Modbus Read Write block will be activated and the x-Messenger could
communicate with peripheral as a master via RS232 , RS485 or Ethernet interface you selected, further
the output will be switched on when the communication is established successfully. Otherwise the output
(Q pin) is keep off it means communication is failed.
A signal at input R resets output Q and disable this block at the same time
Note:
If you are using old Ethernet CPU(need deviceManger to configure the modem) without web server
built-in and you need use MODBUS through Ethernet port, then you still use MODBUS READ or MODBUS
WRITE block. The MODBUS READ WRITE( Ethernet comm type) is only for the new version Ethernet CPU.
Connection
Description
Input
En
A high signal at En input will enable “Modbus Write” function block to be activated
Input
R
Reset the value read from peripheral and set the output to 0 via the R (Reset) input.
Reset has priority over En
Parameter
Slave address: 1 is default .
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...