152
Note: 1.
Data register Index: High Low /Low High
For example, when High Low index was set, one data 0x 00 12 was read and saved to AQ, AQ= 0X0012;
however, when Low High index was set, AQ=0x 1200
Regarding Modbus RTU detail, please refer to our Modbus RTU communication protocol file for it.
Description of the function:
In the configuration of our xLogic communication, the xLogic usually serves as a slave via Modbus RTU
Protocol, and can communicate with a master directly. That’s to say, any device communicating with
xLogic sends command to it, and then its response will be sent out only when the xLogic has received the
command, Just as the below figure shows:
However, the “Modbus Read” or “Modbus Write”(next chapter will introduce it) function block would be
utilized if xLogic shall be required to play a role of master to communicate with other devices. As the
following figure shows:
When you put the “Modbus read” or “Modbus Write” function block in your program and make some
configurations, the function that xLogic serves as master will be realized.
The Property in dialog box of “Modbus Read” shows as below figure:
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...