147
level 1 or level 2 at the acceleration set in Rate.
If the input St is set, the function runs to a level of StSp + B at the acceleration set in Rate. Then the
function holds the level at StSp + Offset "B" for 100 ms. After 100 ms, the level is set to Offset "B". output
AQ. The scaled value (output AQ) is 0.
If the input St is set, the function can only be restarted once the inputs St and En have been reset.
If input Sel has been changed, depending on the connection of Sel, the function runs from the current
target level to the new target level at the rate that is specified.
If the input En is reset, the function immediately sets the current level to Offset "B".
The current level is updated every 100 ms. Note the relationship between output AQ and the current
level:
Output AQ = (current level – Offset "B" ) / Gain "A"
5.5.30 Analog Math
Fashion:
Classic:
Short Description
The analog math block calculates the value AQ of an equation formed from the user-defined operands
and operators.
Connection
Description
Input
EN
Enable the analog math function block.
Parameter
V1:
Value 1: First operand
V2:
Value 2: Second operand
V3:
Value 3: Third operand
V4:
Value 4: Forth operand
Operator 1:
First operator
Operator2:
Second operator
Operator 3:
Third operator
Priority 1:
Priority of first operation
Priority 2:
Priority of second operation
Priority 3:
Priority of third operation
P:
number of decimals
Range of values: 0,1,2,3
Output
AQ
The output AQ is the result of the equation formed from the operand values and
operators. AQ will be set to 32767 if a divide by 0 or overflow occurs, and -32768
if a negative overflow (underflow) occurs.
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...