5.5.33 Modbus Write
Fashion:
Classic:
Short description:
When a high level in En, the Modbus Write block will be activated and the xLogic could communicate with
peripheral as a master via RS232 or RS485 interface, further the output will be switched on when the
communication is established successfully. Otherwise the output (Q pin) is kept“off” it means
communication has failed.
A signal at input R resets output Q and disable, this block at the same time
Connection
Description
Input
En
A high signal at En input will enable “Modbus Write” function block to be activated
Input
R
Reset the value read from peripheral and set the output to 0 via the R (Reset) input.
Reset has priority over En
Parameter
Slave address
: 1 is default .
Communication protocol:
Modbus(RTU)
Communication parameter:
baud rate (BPS),Data bits, Stop bits,
Parity
,
Overtime (response time out)
Comm Type:
RS232 or RS485( Communication interface of xLogic )
Data register Index:
High Low /Low High
Command:
05 Write Single Coil
06 Write Single Register
15 Write Multiple Coils
16 Write Multiple Registers
Register start address, count
Output
Q
Q is set or reset depending on the communication status.
Successful communication , Q=1;
Failed communication ,Q=0;
Note:
This function block(com type: Ethernet) can not be used for the Ethernet
CPU(ELC-12DC-DA-R-N) built-in web server, it is only for the old version, if you are using new
series Ethernet(hardware version:1), please use the MODBUS READ WRITE block instead.
Get the version number by the software menu Tools-> transfer-> Get PLC version
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...