installation
Grandview
®
G600C Gas Fireplace
|
51
1166
22
22
00
0 0
1122
1122
66
66
1188
44
44
1144
88
88
1100
1100
1144
1166
1188
2200
Vertical Height (Feet)
Horizontal (Feet)
Set #2
(1-3/4" open)
Set #1
(2” open)
39-1/2” (1.1 m)
Minimum Height
Requirement
Venting Arrangements - Horizontal Termination - Rigid Pipe and Direct Vent System (Flex)
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
o
elbow (two 45
o
elbows equal one 90
o
elbow).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.
•
Maintain clearances to combustibles.
•
Horizontal vent must be supported every 3 feet.
•
Firestops are required at each floor level and whenever passing through a wall.
Note: FPI Direct Vent Flex System Part
#:946-513 (2 foot or 0.61 m), 946-515
(4 foot or 1.22 m) and 946-516 (10
foot or 3.05 m) only are approved
for horizontal terminations.
All Rigid Pipe System
4" (102 mm) inner diameter
6-5/8" (168 mm) outer diameter
FPI Flex Vent
4" (102 mm) inner diameter
6-7/8" (175 mm) outer diameter
Note: A vent guard should be used when-
ever the termination is lower than
the specified minimum or as per
local codes.