54
|
Grandview
®
G600C Gas Fireplace
installation
Vertical Venting With Two 90
o
Elbows
Vertical Venting With Three 90
o
Elbows
V1
V
H
V
H1
H
V1
One 90
o
elbow = Two 45
o
elbows.
Option
V
H
V + V1
W i t h t h e s e
o p t i o n s ,
maximum total
pipe length is
30 feet with
minimum of
7 feet total
ver tical and
m a x i m u m
8 feet total
horizontal.
Please note
minimum 1
foot between
90
o
elbows is
required.
A)
0' Min.
2' (0.61 m) Max.
1' (0.3 m) Min.
B)
1' (0.3 m) Min.
4' (1.22 m) Max.
3' (0.91 m) Min.
C)
2' (0.61 m) Min.
5' (1.52 m) Max.
4' (1.22 m) Min.
D)
3' (0.91 m) Min. 6' (1.82 m) Max.
5' (1.52 m) Min.
E)
4' (1.22 m)Min. 7' (2.13 m) Max.
6' (1.82 m) Min.
F)
5' (1.52 m) Min. 8' (2.43 m) Max.
7' (2.13 m) Min.
Restrictor Set #1 - 2" (51 mm) open
Lengths do not include elbow indicated.
*Required when using rigid venting
One 90
o
elbow = Two 45
o
elbows.
Option
V
H + H1
V + V1
W i t h t h e s e
o p t i o n s ,
maximum total
p i p e l e n g t h
is 30 feet with
minimum of 10
feet total vertical
and maximum
8 fe e t t o t a l
horizontal.
P l e a s e n o t e
minimum 1 foot
between 90
o
elbows is re-
quired.
A)
0' Min.
2' (0.61 m) Max. 2' (0.61 m) Min.
B)
1' (0.3 m) Min.
2' (0.61 m) Max.
3' (0.91 m) Min.
C)
2' (0.61 m) Min.
3' (0.91 m) Max.
4' (1.22 m) Min.
D)
3' (0.91 m) Min.
4' (1.22 m) Max.
6' (1.82 m) Min.
E)
4' (1.22 m) Min.
5' (1.52 m) Max.
7' (2.13 m) Min.
F)
5' (1.52 m) Min.
6' (1.82 m) Max.
8' (2.44 m) Min.
G)
6' (1.82 m) Min.
7' (2.13 m) Max. 9' (2.74 m) Min.
H)
7' (2.13 m) Min.
8' (2.44 m) Max. 10' (3.05 m) Min.
Restrictor Set #1 - 2" open
Lengths do not include elbow indicated.
*Required when using rigid venting
*
*