installation
Grandview
®
G600C Gas Fireplace
|
23
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
If these clearances (air space) to combustible materials are not adhered to. It is of
greatest importance that this fireplace and vent system be installed only in accordance
with these instructions.
Cool Wall Clearances
The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Minimum Vent Clearances
to Combustibles
G600C Clearance Requirements—Cool Wall Installations
Clearance:
Cool Wall - Clean Front
Measured From:
A: Mantel Height (min.)
1" (25mm)**
Top of Fireplace Opening
B: Sidewall
6" (152mm)
Side of Fireplace Opening
C: Ceiling
44-1/4" (1124mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
12" (305mm)
Front of Fireplace Opening
E: Alcove Width
84" (2134mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
G: Convection Air Outlet
58 in
2
(375cm
2
)*
Top/Front of Enclosure
H: Convection Air Outlet Opening Offset
0-2" (0-51mm)
*Top of Chase Enclosure
K:
Chase Enclosure (Min.)
74-1/2" (1892mm)
From Base of Appliance Floor
L: Clearance to Sprinkler Head (Min.)
36" (914mm)
Perpendicular From Chase Grill
Notes:
0"
No Hearth Required
IMPORTANT - *A minimum of 58 square inches of open area, not lower than 0"-2" from top of enclosure,
required for all cool wall installations — this can be achieved by having an open area in front. See manual
for details.
** An extra 3/4" (19mm)of mantel height is required when using a faceplate.
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)
Alcove
E
F
D
A
E
F
H
G
K
C
Side view
L
Chase grill
Sprinkler
The
HeatWave
Duct Kit
has different clearance
and framing require-
ments, check the
Heat-
Wave
manual for details.