56
|
Grandview
®
G600C Gas Fireplace
installation
Venting Arrangement - Vertical Terminations - Co-linear Flex System Into Masonry Fireplaces
FOR BOTH RESIDENTIAL & MANUFACTURED HOMES
30'
(9.14 m)
Max.
8'
(2,44 m)
Min.
40”
1016 mm
30
Horizontal Distance (Feet)
Vertical Height (feet)
8'
(2,44 m)
Min.
39
-1/2
"
1003 mm
30'
(9.14 m)
Max.
30
Horizontal Distance (Feet)
Vertical Height (feet)
2'
(0,61 m)
max.
Combined min. of 8'
(2.44 m)
6'
(1.82 m)
max.
39
-1/2"
1003 mm
Combined max. of 30'
(9.14 m)
30
Horizontal Distance (Feet)
Vertical Height (feet)
2'
(0.61 m)
max.
IMPORTANT: As shown below, the unit can only be vented from the top, not from the rear.
Restrictor at Set #1 (2" open)