Chapter 3: DXi6902 FRU Removal and Replacement Procedures
Replacing a Node Processor and Heatsink
132
Quantum DXi6902 User’s Guide
Installing a Replacement Network Daughter Card
To install the replacement network daughter card in the DXi6902 Node:
1
Angle the card so that the RJ-45 connectors fit through the slot in
).
2
Align the captive screws at back end of the card with the captive
screw sockets on the system board.
3
Press the touch point on the card until the card connector is firmly
seated on the system board connector.
4
Using a #2 Phillips screwdriver, tighten the two captive screws to
secure the network daughter card to the system board.
5
Replace the quad port SAS card in expansion card riser 2 (see
Replacing an Expansion Card in Riser 2 or 3
6
Close the Node cover (see
7
Turn on the system (see
Turning On and Shutting Down the System
8
Run
Factory Detect Hardware
from the
Service Menu
to detect the
9
In the remote management console, delete any administrative alerts
and close any service tickets.
Replacing a Node Processor and Heatsink
This section describes how to remove and replace a processor (CPU) and
heatsink in the DXi6902 Node and contains the following sections:
•
Obtaining a Replacement Processor and Heatsink
•
Replacing the Processor and Heatsink
Obtaining a
Replacement Processor
and Heatsink
Before beginning the replacement procedure, make sure that you have
the required replacement kit. The appropriate replacement processor
and heatsink will be provided by Quantum Customer Support (see
).
Summary of Contents for DXi6902
Page 1: ...Field Service Manual Quantum DXi6902 with DXi 3 0 0_69 Software 6 68164 01 Rev A...
Page 8: ...Contents viii Quantum DXi6902 User s Guide...
Page 16: ...Tables xvi Quantum DXi6902 User s Guide...
Page 24: ...Preface xxiv Quantum DXi6902 User s Guide...
Page 242: ...Appendix A DXi6902 Cabling Diagrams 218 Quantum DXi6902 User s Guide...