Chapter 3: DXi6902 FRU Removal and Replacement Procedures
Replacing an Array Module Controller
172
Quantum DXi6902 User’s Guide
Installing a Replacement Power Supply in an Array or
Expansion Module
To install the replacement power supply in the DXi6902 Array module
(RBOD) or Expansion module (EBOD):
1
Ensure that the power switch on the new supply is in the off
position (see
WARNING:
To avoid electrical shock, make sure the power cord is
disconnected from the new power supply and the
power switch is off before inserting into the Array or
Expansion module chassis.
2
Slide the replacement power supply into the chassis until the power
supply snaps into place, and push the handles into the closed
position.
3
Connect the power cable to the power supply and plug the cable
into a power outlet.
4
Turn on the power switch.
Allow up to a minute for the system to recognize the power supply
and determine its status. The AC enabled LED turns green to signify
that the power supply is functioning properly.
5
In the remote management console, delete any administrative alerts
and close any service tickets.
Replacing an Array Module Controller
This section describes how to remove and replace a controller in a
DXi6902 Array module (RBOD) and contains the following sections:
•
Obtaining a Replacement Array Module Controller
•
Summary of Contents for DXi6902
Page 1: ...Field Service Manual Quantum DXi6902 with DXi 3 0 0_69 Software 6 68164 01 Rev A...
Page 8: ...Contents viii Quantum DXi6902 User s Guide...
Page 16: ...Tables xvi Quantum DXi6902 User s Guide...
Page 24: ...Preface xxiv Quantum DXi6902 User s Guide...
Page 242: ...Appendix A DXi6902 Cabling Diagrams 218 Quantum DXi6902 User s Guide...