When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-142
RAAA101 Illegal/Undefined
Device Address
A device address in the part or func-
tion settings is illegal. Make sure to
set the correct device address.
—
RAAA102 Failed to read from
the Device/PLC.
(XXXX)
Failed to read from the device/PLC.
Confirm the connection status, such
as whether the communication cable
is disconnected, etc.
The part name is entered in the
parentheses.
)
GP3000 Series
Hardware Manual
RAAA103 The specified
address is incorrect.
(XXXX)
The designated address is incorrect.
Make sure to set the correct address.
—
RAAA110 Remote PC Access
error. Unable to
recover.
An internal initialization error or sys-
tem error occurred. Restart the GP
unit, or review the screen settings.
)
“2.14.9 System
Menu n Offline,
CF Starting, Error,
Reset” (page 2-
156)
RAAA111 Unable to certify
Remote PC Access
server.
The password is invalid. Check if
the password matches the password
specified on the Server PC.
)
GP-Pro EX Refer-
ence Manual
“36.3.2 Setup Pro-
cedure n Proce-
dure” (page 36-7)
RAAA112 Failed to connect to
Remote PC Access
server.
No Server PC is found, or the con-
nection to the Server PC is not estab-
lished. Check if the IP address
matches with that for the Server PC.
Check if the Server PC is active.
Check the settings on the Server PC.
Check if the Server PC Firewall is
enabled.
RAAA113 Connecting to
Remote PC Access
server.
The previous disconnection process
is not completed.
Wait for a while (75 seconds maxi-
mum), and then retry connecting to
the server.
—
RAAA114 Missing remote PC
access license key
code.
With GP-Pro EX, the RPA function
key code has not been set up.
To use the RPA function, you must
purchase a dedicated RPA key code
(model: EX-RPA). Obtain one key
code for each display that uses the
RPA function.
)
GP-Pro EX Refer-
ence Manual
“36.3.2 Setup Pro-
cedure n Proce-
dure” (page 36-7)
RAAA120 D-Script Error (The
specified function
does not exist or the
function has an
error.)
The function called in the D-Script
does not exist. Or there is an error in
the function. Check the function’s
format.
)
GP-Pro EX Refer-
ence Manual
“Chapter 21 Com-
mands and
Descriptions”
(page 21-1)
Continued
Error No.
Error Message
Cause and Solution
Reference