When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-139
Errors starting with RAAA (Application errors)
Error No.
Error Message
Cause and Solution
Reference
RAAA001 No project data
exists. (Transfer a
project.)
No project file exists.
Transfer a project.
)
GP-Pro EX Refer-
ence Manual
“33.2.2 Transfer
Process n Trans-
fer from PC to GP
(Send)” (page 33-6)
)
GP-Pro EX Refer-
ence Manual
“33.3.2 Transfer
Process n Trans-
fer from PC to GP
(Send)” (page 33-
13)
RAAA002 The project data size
exceeds the capac-
ity.
The project data size exceeds the
maximum capacity
∗
. Or, the number
of screens exceeds 16,000 files. Ref-
erence the “Project Information” in
GP-Pro EX, and make sure it does
not exceed the general capacity.
∗
The maximum capacity of the
project data size varies depending on
the Display model. (Example: 8 MB
for GP-3500T).
)
GP-Pro EX Refer-
ence Manual “5.7
Viewing Project
Information” (page
5-41)
RAAA003 The project data is
invalid. (Transfer the
project again.)
There is an error in the project file.
Transfer the project again.
)
GP-Pro EX Refer-
ence Manual
“33.2.2 Transfer
Process n Trans-
fer from PC to GP
(Send)” (page 33-6)
)
GP-Pro EX Refer-
ence Manual
“33.3.2 Transfer
Process n Trans-
fer from PC to GP
(Send)” (page 33-
13)
RAAA004 The system screen
is invalid. (Execute
forced transfer.)
The system screen does not exist or
is invalid.
Force a transfer.
)
GP-Pro EX Refer-
ence Manual
“33.10.1 [Transfer
Settings] Settings
Guide” (page 33-
59)
RAAA005 The specified initial
screen no. does not
exist. (XXXX)
The screen cannot display because
the screen number designated in the
Initial Screen Settings does not exist
in the project. Change the Initial
Screen No. or add the screen. The
screen number designated in the
parentheses is displayed.
)
GP-Pro EX Refer-
ence Manual
“5.14.6 [System
Settings] Setting
Guide u Display”
(page 5-112)
Continued