When an error message is displayed (Error code list)
Maintenance/Troubleshooting
1-141
RAAA011 Failed to start from
the CF card.
Regardless of whether DIP SW1 is
ON, the necessary file does not exist to
start from the CF-card. Or the neces-
sary file may have an error. Copy the
startup project to the CF-card again.
—
RAAA012 The project data
contains functions
that are not sup-
ported by this model.
The current model includes func-
tions which the runtime program
cannot recognize. Change to an
applicable model.
RAAA013 USB storage loca-
tion not found.
The USB storage device cannot be
accessed due to the poor connection
or recognition problem. Check if the
USB storage device is connected. If
connected, disconnect and then
reconnect the USB storage device.
RAAA014 Failed to start from
USB storage.
The file required for startup from the
USB storage device does not exist,
or the file required for startup may
be defective. Copy the required star-
tup project onto the USB storage
device again.
RAAA050 Clock Setting Error
When changing the clock data, the
data write to the clock IC failed.
The IC chip may be broken.
RAAA051 Low battery
Due to the low voltage of the backup
lithium battery, the backup SRAM’s
data is erased, and the clock data
will not be correctly kept.
Supply enough power to the GP and set
the clock data again. The battery requires
24 hours of charging to reach a level that
allows backup operation, and about 96
hours (4 days) to be fully charged.
)
GP3000 Series
Hardware Manual
RAAA052 There is a problem
with the hardware.
(XXXX)
(XXXX) indicates where the problem
is in the Display. (Example: When an
error occurred with the LAN port,
“LAN” is displayed.) This may be
caused by a fault in the GP unit. Please
contact your local GP distributor.
—
RAAA100 The system start
device address is
incorrect.
The system device start address is
not set correctly or has an error.
Set the correct address while offline,
or transfer a project.
)
Continued
Error No.
Error Message
Cause and Solution
Reference