perma PRO C
- 18 -
6.10 Impulse Mode via the Connected Control System
Discharge of lubricator PRO C can also be triggered via the attached control system.
In this case, the lubricator discharges 0.5 cm
3
lubricant to the lubrication point every time it is switched on.
For this, you have to switch on the supply voltage via your control system for at least 14 minutes and then you
have to switch it off for at least 20 seconds.
The minimum operating time of 14 minutes is due to the possibility to connect the perma PRO C to the distributor
perma MP-6. This distributor is able to supply lubricant to up to six lubrication points.
This means that the distributor needs a minimum operating time of 14 minutes to be able to supply 1.0 cm
3
lubricant to every open distributor outlet.
If operated as a single-point lubrication system, the minimum operating time is reduced to 1 minute and the
discharge amount per impulse = 0.5 cm
3
.
For an activation of the perma PRO C lubricator via your control system, you need to set the lubricator
to impulse mode via the configuration menu (refer to chapter 6.8).
For this, you have to select the setting “ “ Days in the setting mode “Days” (refer to figure 17).
88
Outlets
1
3
2
4
5
6
Days
Weeks
Months
%Vol.
LC250
0
LC
2
500
Confi g.
Time
Time
PIN
Config.
Time
Days
figure 17
7.
Replacement of the PRO LC unit
The Following Must Always Be Taken into Account
If the replacement of an empty PRO LC unit becomes necessary, it will be indicated by a simultaneous
blinking of the red and the green LED. Additionally, the display indicates that the PRO LC unit is empty
(refer to figure 18).
If the PRO LC unit is empty, the connected control system of your equipment receives a “Low” signal and a
malfunction is indicated.
%Vol.
LC 500
figure 18
If you replace the PRO LC unit by an PRO LC unit of a different size, a corresponding protection cover
(refer to ”Accessories and Spare Parts”) must be used.
Since the drive unit and the control board must be protected against moisture, an exchange may only
be carried out in dry conditions!
After the installation of the new PRO LC unit, the control system continues to operate using the previously valid
setting of the discharge period.
Summary of Contents for Distributor PRO MP-6
Page 3: ...Chap 4 3 perma PRO MP 6 Distributor Drilling template...
Page 4: ...45 75 66 5 6 5 Drilling template Screws M6 2x Fasting points 3x Fasting points...
Page 77: ...Chap 4 3 perma PRO MP 6 Distributor Drilling template...
Page 78: ...45 75 66 5 6 5 Drilling template Screws M6 2x Fasting points 3x Fasting points...