perma PRO MP-6 Distributor
- 16 -
Indication
of the
display
Error
Possible cause
Remedial measures
E0
Lubrication system has been
switched off
Excess motor current of the perma
MP-6
Replace perma MP-6 distributor
F I
to
f6
Error at the displayed
lubrication point
Excess motor current of the
lubricator motor caused by a
blocking of the displayed outlet
Clear the blockage and
acknowledge the fault by
pushing and holding down the
ON/OFF/SELECT or SELECT
button
E2
Lubrication system has been
switched off
Outlets of distributor not correctly
recognized
Replace distributor
E3
Lubrication system has been
switched off
Timeout while activating distributor
Connection cable damaged
Replace distributor
Replace connection cable
e4
Lubrication system has been
switched off
Drive mechanism of the lubricator
is defective
Replace the drive unit of the
lubricator
E5
Outlet configuration missing
Outlets were not activated
Activate desired outlets
(Turn off power supply on
PRO C before you acknowledge
error messages)
LC
Lubrication system does not detect
the PRO LC unit
No PRO LC unit installed
Install an PRO LC unit
(Observe the Operating
Instructions of the lubricator)
L
(Only with
PRO)
No power supplied to the
lubrication system
No power supplied to the lubricator
Establish a power supply
(Observe the Operating
Instructions of the lubricator)
chart 3
6.
Trouble Shooting
6.1
Error Messages of the Distributor on the Display of the Lubricator
Possible errors of the distributor and the complete lubrication system are detected by the electronic control unit
and are indicated on the display of the lubricator. For example, if the error message is shown on the display,
the required pressure at the second connected lubrication point exceeds 25 bar (360psi).
This means that this lubrication point is no longer supplied with lubricant. The distributor still provides lubricant
to all other activated lubrication points. Correct the malfunction of the second lubrication point (e.g. grease line
bent or blocked) and acknowledge it by pushing the ON/OFF/SELECT button on the lubricator PRO or the
SELECT button on lubricator PRO C.
Error messages are acknowledged and reset by pushing the ON/OFF/SELECT or SELECT button.
6.2
Trouble Shooting Guide
If there are malfunctions during the operation of the distributor or the lubrication system, please check for pos-
sible causes using the following chart (refer to chart 3). If you have to deal with a malfunction that is not listed
in the chart below, please contact your local supplier for technical support.
Every time that an error message is shown on the display of the lubricator, the red LED at the lubricator
is also blinking.
Summary of Contents for Distributor PRO MP-6
Page 3: ...Chap 4 3 perma PRO MP 6 Distributor Drilling template...
Page 4: ...45 75 66 5 6 5 Drilling template Screws M6 2x Fasting points 3x Fasting points...
Page 77: ...Chap 4 3 perma PRO MP 6 Distributor Drilling template...
Page 78: ...45 75 66 5 6 5 Drilling template Screws M6 2x Fasting points 3x Fasting points...