Mounting Direction and Space Requirements
・ Allow enough space to ensure enough cooling.
・Install fans to provide a uniform distribution of temperature in the control box.
・ Observe the environmental requirements for the control box, mentioned in the
previous page.
Before Use
< Notes >
Conformance to UL Standard
Observing the following instruction makes this driver a UL508C standard authorized
and EN50178 approved product.
1 Instructions in wiring
(1)Use copper conductor wire with the rated temperature of 60℃ or higher for
wiring to terminal blocks or grounding terminals.
(2)Be sure to connect the protective grounding of the control panel(PE) to a protective
grounding terminal( ) of the driver to prevent electric shock. Do not double-connect to
the protective grounding terminals ( ).Two protective grounding terminals are provided.
2 Overload protection level
The overload protective function of the driver is activated when the effective current
of the driver is 115% or more of the rated current. Make sure that the effective
current of the driver dose not exceed the rated current. The maximum allowable instantaneous
current of the driver is the current set by the torque limit setting(Pr06).
3 Installation environment
Use the driver in environment with the pollution level 2 higher provided in IEC60664-1.For
example,installing in a control panel of IP54 makes the pollution level of the environment 2.
To achieve IP54,the structure shall not allow water,oil,carbon or dust to enter.
min.
40mm
min.
100mm
min.
40mm
min.
100mm
min.
10mm
Fan
Fan
min.
10mm
min.
10mm
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com