20
−
System Configuration and Wiring
List of Available Components
Terminals
on the
terminalblock
M4
M5
Magnetic contactor
(contacts)
BMFT61041N
(3P+1a)
BMFT61541N
(3P+1a)
BMFT61042N
(3P+1a)
BMFT61042N
(3P+1a)
BMFT61542N
(3P+1a)
BMFT61842N
(3P+1a)
B M F 6 2 5 2 N
(3P+2a2b)
B M 6 3 5 2 N
(3P+2a2b)
Noise
filter
LF-210
LF-215
LF-230
LF-305
LF-310
LF-310
LF-315
LF-320
LF-330
LF-340
Non-fuse
breaker
(rated current)
BBP2-10
(10A)
BBP2-15
(15 A)
BBP2-30
(30A)
BBP3-5
(5A)
BBP3-10
(10A)
BBP3-10
(10A)
BBP3-15
(15A)
BBP3-20
(20A)
BBP3-30
(40A)
BBP3-40
(40A)
Output
30〜50W
100W
200W
400W
100W
200W
400W
750W
300W
400W
500W
600W
750W
900W
1.0kW
1.2kW
1.5kW
2.0kW
Voltage
100V
200V
200V
Control
powerwire
diameter (r and t)
0.75mm
2
A. W. G. 18
0.75mm
2
A. W. G. 18
Series
MSDA
MSDA
MQDA
MSDA
MQDA
MSDA
MQDA
MSDA
MGDA
MFDA
MHDA
MGDA
MDDA
MFDA
MGDA
MSDA
MDDA
MHDA
MGDA
MSDA
MDDA
MHDA
MFDA
MSDA
MDDA
MHDA
MGDA
Driver
Main circuit wire diameter
(L1, L2, L3, U,
V, W and E)
0.75mm
2
〜2.0mm
2
A. W. G.
14〜18
0.75mm
2
〜2.0mm
2
A. W. G.
14〜18
2.0mm
2
A. W. G. 14
Required Power
(at the rated load)
approx. 0.3kVA
approx. 0.4kVA
approx. 0.5kVA
approx. 1.0kVA
approx. 0.3kVA
approx. 0.5kVA
approx. 0.9kVA
approx. 1.3kVA
approx. 0.7kVA
approx. 1.0kVA
approx. 1.0kVA
approx. 1.1kVA
approx. 1.3kVA
approx. 1.8kVA
approx. 2.3kVA
approx. 3.3kVA
approx. 3.8kVA
・ When these wires are used, wire lenght between circuit
breaker and driver should be less than 3m.
・ Chose suitable wire size for Earthing Cnductor which has
some dimension as wire for power input and output.