− App.
54
−
You can select whether or not to activate the under-voltage trip
in case the main power is shut-off.
See "Timing chart for the mains and control power shut off" in
Appendix.
You can set-up the conditions for decelerating the motor after
the over-travel limit input (CCWL: CNI/ F Pin 9 or CWL: CN I/F Pin
8) is made active.
You can set-up the conditions of the following operations after
main power off.
① Decelerating and halting the motor
② Clearing the position error counter
(DB: Dynamic brake engaged)
PrNo.
Parameter Range
Function
description
65
66
67
UVtrip selection at
main power-off
DB inhibition at
overtravel limit
Sequence at
main power-off
0 〜 1
【1】
0 〜 1
【0】
0 〜 7
【0】
駆動条件
Motor operation from deceleration to and after stop
The dynamic brake (DB) is activated, and the motor is stopped. After stop,
the dynamic brake is released.
Without dynamic brake the motor stops after coasting.
After stop, the motor remains free.
Value
0
1
Details of Parameters
Under-voltage protective function
If the main power is lost during Servo-ON, Servo-OFF get active (the motor
does not trip). After this, when the main power is on, Servo-ON will be made
active again.
If the main power is lost during Servo-ON, the under-voltage protective func-
tion (Err-13) is activated, and the motor trips.
Value
0
1
Value
0
1
2
3
4
5
6
7
After stop
DB
DB
Free (DB not engaged)
Free (DB not engaged)
DB
DB
Free (DB not engaged)
Free (DB not engaged)
Content of the position
error counter
Cleared
↑
↑
↑
Held
↑
↑
↑
During deceleration
DB
Free run (coasting)
DB
Free run (coasting)
DB
Free run (coasting)
DB
Operating conditions
Free run (coasting)