− App.
44
−
Command pulse
inhibit input
invalidation
Output pulses
per single turn
You can select enabled or disabled of the command pulse inhibit
input (INH: CN I/F Pin 33).
You can set-up encoder pulse counts per single turn, which is to
be fed-out to the controller. Setting in scalar.Set the required pulse
counts per single turn in [Pulse/rev] unit directly. Note that the
set-up of the larger counts than the encoder pulses is disabled.
Details of Parameters
Maximum permissible frequency and minimum required time width of command pulse inputs
Make both of the rising and tailing time 0.1 μs or shorter.
I/F for inputting
PULSE/SIGN signals
Interface for
line drivers
Interface for
open collectors
t
1
2
5
t
2
1
2.5
t
3
1
2.5
t
4
1
2.5
t
5
1
2.5
t
6
1
2.5
Maximum
permissible frequency
500kps
200kpps
Minimum required time width [μs]
Command pulse input is disabled by opening the connection between INH input and
COM-. If you do not use INH inputs, set Pr43 to 1. With this setting, you do not have to
externally connect between INH (CN I/F Pin 33) and COM- (Pin 41).
Value
0
1
INH input
enabled
disabled
PrNo.
Parameter Range
Function
description
42
43
44
0 〜 1
【1】
1 〜
16384
【2500】
(continued)