Pulse Train I/O: H6
User constants for pulse I/O are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H6-01
Pulse train
input func-
tion selec-
tion
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2
0
No
A
A
A
A
A
42CH
6-2
6-29
6-96
Pulse Input
Sel
H6-02
Pulse train
input scal-
ing
Set the number of pulses in
hertz, taking the reference to be
100%.
1000 to
32000
1440
Hz
Yes
A
A
A
A
A
42DH
6-2
6-29
PI Scaling
H6-03
Pulse train
input gain
Set the input gain level as a per-
cent when the pulse train set in
H6-02 is input.
0.0 to
1000.0
100.0%
Yes
A
A
A
A
A
42EH
6-29
Pulse Input
Gain
H6-04
Pulse train
input bias
Set the input bias when the
pulse train is 0.
-100.0
to
100.0
0.0%
Yes
A
A
A
A
A
42FH
6-29
Pulse Input
Bias
H6-05
Pulse train
input filter
time
Set the pulse train input pri-
mary delay filter time constant
in seconds.
0.00 to
2.00
0.10
s
Yes
A
A
A
A
A
430H
6-29
PI Filter
Time
H6-06
Pulse train
monitor
selection
Select the pulse train monitor
output items (value of the
part of U1-
).
There are two types of monitor
items: Speed-related items and
PID-related items.
1, 2, 5,
20, 24,
36
2
Yes
A
A
A
A
A
431H
6-79
Pulse Out-
put Sel
H6-07
Pulse train
monitor
scaling
Set the number of pulses output
when speed is 100% in hertz.
Set H6-06 to 2, and H6-07 to 0,
to make the pulse train monitor
output synchronously to the
output frequency.
0 to
32000
1440
Hz
Yes
A
A
A
A
A
432H
6-79
PO Scaling