5
-90
Note Inverters with a capacity of 185 kW or more are under development.
* 1. The initial settings for C6-02 are as follows: 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, 6: 15 kHz, and F: User-set (Initial setting for
400-V Inverters with a capacity of 90-kW or 110-kW: 3 kHz.).
* 2. The initial settings for C6-11 are as follows: 1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
Con-
stant
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
55
75
90
110
132
160
o2-04
kVA selection
-
2F
30
31
32
33
34
b8-03
Energy-saving filter time
constant
s
2.00 (Open-loop vector control)
b8-04
Energy-saving coefficient
-
67.20
46.20
38.91
36.23
32.79
30.13
C6-02
Carrier frequency selec-
tion
*1
-
2
2
F
F
1
1
C6-11
Carrier frequency selection
for open-loop vector control
2
*2
-
2
2
1
1
1
1
-
Carrier frequency selection
upper limit
-
5.0
5.0
3.0
3.0
2.0
2.0
E2-01
(E4-01)
Motor rated current
A
95.0
130.0
156.0
190.0
223.0
270.0
E2-02
(E4-02)
Motor rated slip
Hz
1.46
1.39
1.40
1.40
1.38
1.35
E2-03
(E4-03)
Motor no-load current
A
24.0
36.0
40.0
49.0
58.0
70.0
E2-05
(E4-05)
Motor line-to-line resis-
tance
Ω
0.088
0.092
0.056
0.046
0.035
0.029
E2-06
(E4-06)
Motor leak inductance
%
20.0
20.0
20.0
20.0
20.0
20.0
E2-10
Motor iron loss for torque
compensation
W
1260
1600
1760
2150
2350
2850
L2-02
Momentary power loss ride-
thru time
s
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock (BB) time
s
1.3
1.5
1.7
1.7
1.8
1.9
L2-04
Voltage recovery time
s
1.0
1.0
1.0
1.0
1.0
1.0
L8-02
Overheat pre-alarm level
°
C
100
105
105
120
115
115
N5-02
Motor acceleration time
s
0.317
0.533
0.592
0.646
0.673
0.777