5
-84
* 1. The settings will be 0.05 (Flux vector)/2.00 (Open-loop vector) for inverters of 55kW or larger.
* 2. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
* 3. Settings vary as shown in the following tables depending on the Inverter capacity and E1-03.
* 4. The setting range is 0 to 66.0 for open-loop vector control 2.
200 V and 400 V Class Inverters of 0.4 to 1.5 kW
* The setting shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
200 V and 400 V Class Inverters of 2.2 to 45 kW
* The setting shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
E1-09
E3-07
Min. output frequency (FMIN)
0.0 to 400.0
0.1 Hz
1.5
*3
1.5
*3
0.5
0.0
0.3
Min Frequency
E1-10
E3-08
Min. output frequency voltage (VMIN)
*2
0.0 to 255.0
(0.0 to 510.0)
0.1 V
9.0
*3
9.0
*3
2.0
0.0
1.0
Min Voltage
F1-09
Overspeed detection delay time
0.0 to 2.0
0.1 s
-
1.0
-
0.0
0.0
PG Overspd Time
N5-01
Feed forward control selection
0, 1
1
-
-
-
0
1
Feedfoward Sel
Con-
stant
Num-
ber
Unit
Factory Setting
Open
Loop
Vector
Con-
trol
1
Open
Loop
Vector
Con-
trol
2
Flux
Vector
Con-
trol
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04 Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0 180.0
60.0
60.0
60.0
60.0
E1-05
*
V
200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
E1-06 Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
0.0
E1-07 Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
E1-08
*
V
15.0
15.0
15.0
15.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
15.0
15.0
15.0
15.0
11.0
13.3
0.0
E1-09 Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.3
0.0
E1-10
*
V
9.0
9.0
9.0
9.0
8.0
9.0
8.0
9.0
11.0
13.0
11.0
15.0
9.0
9.0
9.0
9.0
2.0
1.3
0.0
Con-
stant
Num-
ber
Unit
Factory Setting
Open
Loop
Vector
Con-
trol
1
Open
Loop
Vector
Con-
trol
2
Flux
Vector
Con-
trol
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04 Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0 180.0
60.0
60.0
60.0
60.0
E1-05
*
V
200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
E1-06 Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
0.0
E1-07 Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
E1-08
*
V
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
14.0
11.0
13.3
0.0
E1-09 Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.3
0.0
E1-10
*
V
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
7.0
2.0
1.3
0.0
Con-
stant
Number
Name
Setting Range
Unit
Factory Setting
Display
V/f
Control
V/f with
PG
Open-
loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Summary of Contents for VARISPEED G7 -
Page 3: ......
Page 11: ...viii...
Page 33: ...1 16...
Page 105: ...4 20...
Page 349: ...6 154...
Page 375: ...7 26...
Page 413: ...10 24...
Page 417: ......