5
-42
Analog Monitor Cards: F4
User constants for the Analog Monitor Card are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F4-01
Channel 1
monitor
selection
Effective when the Analog
Monitor Card is used.
Monitor selection:
Set the number of the monitor
item to be output. (U1-
)
Gain:
Set the multiple of 10 V for
outputting monitor items.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used. When the AO-
12 Analog Monitor Card is
used, outputs of ± 10 V are
possible. To output ± 10 V, set
F4-07 or F4-08 to 1. When
the AO-08 Analog Monitor
Card is used, only outputs of
0 to +10 V are possible.
A meter calibration function
is available.
1 to 45
2
No
A
A
A
A
A
391H
6-77
AO Ch1
Select
F4-02
Channel 1
gain
0.00 to
2.50
1.00
Yes
A
A
A
A
A
392H
6-77
AO Ch1 Gain
F4-03
Channel 2
monitor
selection
1 to 45
3
No
A
A
A
A
A
393H
6-77
AO Ch2
Select
F4-04
Channel 2
gain
0.00 to
2.50
0.50
Yes
A
A
A
A
A
394H
6-77
AO Ch2 Gain
F4-05
Channel 1
output moni-
tor bias
Sets the channel 1 item bias
to 100%/10 V when the ana-
log monitor card is used.
-10.0 to
10.0
0.0%
Yes
A
A
A
A
A
395H
6-77
AO Ch1 Bias
F4-06
Channel 2
output moni-
tor bias
Sets the channel 2 item bias
to 100%/10 V when the ana-
log monitor card is used.
-10.0 to
10.0
0.0%
Yes
A
A
A
A
A
396H
6-77
AO Ch2 Bias
F4-07
Analog out-
put signal
level for
channel 1
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
A
397H
-
AO Opt
Level Sel
F4-08
Analog out-
put signal
level for
channel 2
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
A
398H
6-77
AO Opt
Level Sel