Continuing Operation
6-
57
* 1. The factory setting will change when the control method is changed. (Open-loop vector control 1 factory settings are given.)
* 2. Factory settings depend on Inverter capacity. (The values shown are for a 200 V Class Inverter for 0.4 kW.)
Multi-function Contact Inputs (H1-01 to H1-10)
b3-02
Speed search
operating cur-
rent (current
detection)
Sets the speed search operation cur-
rent as a percentage, taking the
Inverter rated current as 100%.
Not usually necessary to set. When
restarting is not possible with the
factory settings, reduce the value.
0 to
200
100%
*1
No
A
No
A
No
A
SpdSrch Cur-
rent
b3-03
Speed search
deceleration
time (current
detection)
Sets the output frequency decelera-
tion time during speed search in 1-
second units.
Set the time for deceleration from
the maximum output frequency to
the minimum output frequency.
0.1 to
10.0
2.0 s
No
A
No
A
No
No
SpdSrch Dec
Time
b3-05
Speed search
wait time
(current detec-
tion or speed
calculation)
Sets the contactor operating delay
time when there is a contactor on
the output side of the Inverter.
When a speed search is performed
after recovering from a momentary
power loss, the search operation is
delayed by the time set here.
0.0 to
20.0
0.2 s
No
A
A
A
A
A
Search Delay
L2-03
Min. base-
block time
Sets the Inverter's minimum base-
block time in units of one second,
when the Inverter is restarted after
power loss ridethrough.
Sets the time to approximately 0.7
times the motor secondary circuit
time constant.
When an overcurrent or overvolt-
age occurs when starting a speed
search or DC injection braking,
increase the set values.
0.1 to
5.0
0.5 s
*2
No
A
A
A
A
A
PwrL Base-
block t
L2-04
Voltage recov-
ery time
Sets the time required to return the
Inverter output voltage to normal
voltage at the completion of a speed
search, in units of one second.
Sets the time required to recover
from 0 V to the maximum voltage.
0.0 to
5.0
0.3 s
*2
No
A
A
A
A
A
PwrL V/F
Ramp t
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
61
External search command 1 (ON: Speed search from maximum output frequency)
Yes
No
Yes
No
Yes
62
External search command 2 (ON: Speed search from set frequency)
Yes
No
Yes
No
Yes
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
Summary of Contents for VARISPEED G7 -
Page 3: ......
Page 11: ...viii...
Page 33: ...1 16...
Page 105: ...4 20...
Page 349: ...6 154...
Page 375: ...7 26...
Page 413: ...10 24...
Page 417: ......