Monitor Constants
6-
77
Selecting Analog Monitor Items
The digital operator monitor items (U1-
[status monitor]) are output from multi-function analog output
terminals FM-AC and AM-AC. Refer to
Chapter 5 User Constants
, and set the values for the
part of U1-
(status monitor).
Alternatively, you can output monitor items (U1-
[status monitor]) from analog output option terminal
channels 1 and 2 on analog monitor cards AO-08 and AO-12. Refer to the table of constants, and set the val-
ues.
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level for
multi-function output 1 (terminal
FM)
0: 0 to +10 V output
1: 0 to ±10 V output
0 or 1
0
No
A
A
A
A
A
AO Level
Select1
F4-01
Channel 1
monitor
selection
Effective when the Analog Monitor
Card is used.
Monitor selection:
Set the number of the monitor item
to be output. (U1-
)
Gain:
Set the multiple of 10 V for output-
ting monitor items.
4, 10 to 14, 25, 28, 34, 39, 40 cannot
be set. 29 to 31 and 41 are not used.
When the AO-12 Analog Monitor
Card is used, outputs of ± 10 V are
possible. To output ± 10 V, set F4-
07 or F4-08 to 1. When the AO-08
Analog Monitor Card is used, only
outputs of 0 to +10 V are possible.
A meter calibration function is
available.
1 to 45
2
No
A
A
A
A
A
AO Ch1
Select
F4-02
Channel 1
gain
0.00 to
2.50
1.00
Yes
A
A
A
A
A
AO Ch1 Gain
F4-03
Channel 2
monitor
selection
1 to 45
3
No
A
A
A
A
A
AO Ch2
Select
F4-04
Channel 2
gain
0.00 to
2.50
0.50
Yes
A
A
A
A
A
AO Ch2 Gain
F4-05
Channel 1
output moni-
tor bias
Sets the channel 1 item bias to
100%/10 V when the analog moni-
tor card is used.
-10.0 to
10.0
0.0
Yes
A
A
A
A
A
AO Ch1 Bias
F4-06
Channel 2
output moni-
tor bias
Sets the channel 2 item bias to
100%/10 V when the analog moni-
tor card is used.
-10.0 to
10.0
0.0
Yes
A
A
A
A
A
AO Ch2 Bias
F4-07
Analog out-
put signal
level for
channel 1
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
A
AO Opt
Level Sel
F4-08
Analog out-
put signal
level for
channel 2
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0
No
A
A
A
A
A
AO Opt
Level Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2