5
-40
Analog Reference Card: F2
User constants for the Analog Reference Card are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F1-12
Number of
PG gear teeth
1
Sets the number of teeth on
the gears if there are gears
between the PG and the
motor.
A gear ratio of 1 will be used
if either of these constants is
set to 0.
0 to
1000
0
No
No
A
No
No
No
38BH
6-
143
PG # Gear
Teeth1
F1-13
Number of
PG gear teeth
2
0
No
No
A
No
No
No
38CH
6-
143
PG # Gear
Teeth2
F1-14
PG open-cir-
cuit detection
time
Used to set the PG disconnec-
tion detection time. PGO will
be detected if the detection
time continues beyond the set
time.
0.0 to
10.0
2.0 s
No
No
A
No
A
No
38DH
6-
143
PGO Detect
Time
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F2-01
Bi-polar or
uni-polar
input selec-
tion
Sets the functions for channel
1 to 3 which are effective
when the AI-14B Analog
Reference Card is used.
0: 3-channel individual
(Channel 1: terminal A1,
Channel 2: terminal A2,
Channel 3: terminal A3)
1: 3-channel addition (Addi-
tion values are the fre-
quency reference)
When set to 0, select 1 for b1-
01. In this case the multi-
function input “Option/
Inverter selection” cannot be
used.
0 or 1
0
No
A
A
A
A
A
38FH
6-
149
AI-14 Input
Sel