5
-26
Reference Constants: d
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d1-01
Frequency
reference 1
Sets the frequency reference
in the units used in o1-03.
0 to
400.00
*
0.00 Hz
Yes
Q
Q
Q
Q
Q
280H
4-6
6-5
Reference 1
d1-02
Frequency
reference 2
The frequency reference
when multi-step speed refer-
ence 1 is ON for a multi-func-
tion input.
0.00 Hz
Yes
Q
Q
Q
Q
Q
281H
4-6
6-5
Reference 2
d1-03
Frequency
reference 3
The frequency reference
when multi-step speed refer-
ence 2 is ON for a multi-func-
tion input.
0.00 Hz
Yes
Q
Q
Q
Q
Q
282H
4-6
6-5
Reference 3
d1-04
Frequency
reference 4
The frequency reference
when multi-step speed refer-
ences 1 and 2 are ON for
multi-function inputs.
0.00 Hz
Yes
Q
Q
Q
Q
Q
283H
4-6
6-5
Reference 4
d1-05
Frequency
reference 5
The frequency when multi-
step speed reference 3 is ON
for a multi-function input.
0.00 Hz
Yes
A
A
A
A
A
284H
6-5
Reference 5
d1-06
Frequency
reference 6
The frequency reference
when multi-step speed refer-
ences 1 and 3 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
285H
6-5
Reference 6
d1-07
Frequency
reference 7
The frequency reference
when multi-step speed refer-
ences 2 and 3 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
286H
6-5
Reference 7
d1-08
Frequency
reference 8
The frequency reference
when multi-step speed refer-
ences 1, 2, and 3 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
287H
6-5
Reference 8
d1-09
Frequency
reference 9
The frequency reference
when multi-step speed refer-
ence 4 is ON for a multi-func-
tion input.
0.00 Hz
Yes
A
A
A
A
A
288H
-
Reference 9
d1-10
Frequency
reference 10
The frequency reference
when multi-step speed refer-
ences 1 and 4 are ON for
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
28BH
-
Reference 10
d1-11
Frequency
reference 11
The frequency reference
when multi-step speed refer-
ences 2 and 4 are ON for a
multi-function inputs.
0.00 Hz
Yes
A
A
A
A
A
28CH
-
Reference 11
Summary of Contents for VARISPEED G7 -
Page 3: ......
Page 11: ...viii...
Page 33: ...1 16...
Page 105: ...4 20...
Page 349: ...6 154...
Page 375: ...7 26...
Page 413: ...10 24...
Page 417: ......