6
-96
b5-12
Selection of
PID feedback
command loss
detection
0: No detection of loss of PID
feedback.
1: Detection of loss of PID
feedback.
Operation continues during
detection, with the
malfunctioning contact not
operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault contact
operates.
0 to 2
0
No
A
A
A
A
A
Fb los Det Sel
b5-13
PID feedback
command loss
detection level
Sets the PID feedback loss detec-
tion level as a percent units, with
the maximum output frequency at
100%.
0 to 100
0%
No
A
A
A
A
A
Fb los Det Lvl
b5-14
PID feedback
command loss
detection time
Sets the PID feedback loss detec-
tion level in s units.
0.0 to
25.5
1.0 s
No
A
A
A
A
A
Fb los Det Time
b5-15
PID sleep func-
tion operation
level
Set the PID sleep function start
level as a frequency.
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
PID Sleep
Level
b5-16
PID sleep oper-
ation delay time Set the delay time until the PID
sleep function starts in seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
A
PID Sleep Time
b5-17
Accel/decel
time for PID
reference
Set the accel/decel time for PID
reference in seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
A
PID SFS Time
H6-01
Pulse train
input function
selection
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2
0
No
A
A
A
A
A
Pulse Input Sel
Con-
stant
Number
Name
Description
Output Signal Level Dur-
ing Multi-Function Ana-
log Output
Min.
Unit
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
U1-24
PID feed-
back value
Monitors the feedback value
when PID control is used.
The input for the max. frequency
corresponds to 100%.
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
A
A
A
A
A
PID Feed-
back
U1-36
PID input
volume
PID feedback volume
Given as maximum frequency/
100%
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
A
A
A
A
A
PID Input
U1-37
PID output
volume
PID control output
Given as maximum frequency/
100%
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
A
A
A
A
A
PID Output
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2