57
V530-R160
Operation Manual
SE
C
T
IO
N
3
Conn
ect
ing th
rough
th
e Par
a
lle
l I/O
SECTION 3
Connection to the Host
Note: Pins A9 to A11 and B9 to B10 are for control signals.
Do not use RESET input immediately after power is turned ON. When using RESET input to syn-
chronize execution timing, wait at least 1 second after turning ON the V530-R160 power supply
before turning ON the RESET terminal.
Use DC power supplies with safe extra low-voltage circuits for COMIN in order to prevent high volt-
ages. If UL recognition is required, use a UL class II power supply.
Pin
Signal
Wire
color
Marking
(Black)
Function
Pin
Signal
Wire
color
Marking
(Red)
Function
A1
RESET
Light
brown
Restarts the
V530-R160.
B1
COMIN
Light
brown
Common for
input signals
A2
TRIG A
Yellow
Trigger input
(One shot
reading)
B2
DSA
Yellow
Do not use.
A3
TRIG B
Green
Trigger input
(Continuous/
level trigger)
B3
TRIG C
Green
Trigger input
(Scene setting,
level trigger)
A4
TRIG D
Gray
Trigger input
(Scene set-
ting, level trig-
ger)
B4
−
Gray
Do not use.
A5
−
White
Do not use.
B5
−
White
A6
−
Light
brown
B6
−
Light
brown
A7
−
Yellow
B7
−
Yellow
A8
−
Green
B8
−
Green
A9
RUN
Gray
ON while in
RUN mode
B9
ERROR
Gray
ON when an
error has
occurred
A10 BUSY
White
ON during
processing
B10 GATE
White
ON for the set
output time
A11 OK/NG
Light
brown
Outputs read-
ing judge-
ments
B11 COMOUT1
Light
brown
Common for
control signals
(See note.)
A12 DO0
Yellow
Do not use.
B12 DO1
Yellow
Do not use.
A13 DO2
Green
B13 DO3
Green
A14 DO4
Gray
B14 DO5
Gray
A15 DO6
White
B15 DO7
White
A16 DO8
Light
brown
B16 COMOUT2
Light
brown
Common for
DO0 to DO7
A17 DO9
Yellow
B17 DO10
Yellow
Do not use.
A18 DO11
Green
B18 DO12
Green
A19 DO13
Gray
B19 DO14
Gray
A20 ALARM
White
ON when a
Trend Moni-
tor error
occurs.
B20 COMOUT3
White
Common for
DO9 to DO15