13 Troubleshooting
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
13-5 Even
t L
o
g
s
13
13-5-3 Error Descr
iptions
Event name
IP Address Duplication Error
Event code
84E0 0000 hex
Meaning
The same IP address is used more than once.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
After determining
IP addresses
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
EtherNet/IP communications are not possible. Error
responses are returned to all communications requests.
Data refreshing with the PLC Function Module will con-
tinue.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The IP address of the EtherNet/IP
port is also used as the IP address of
another node.
Perform either of the following and
then cycle the power supply to the
Controller or reset the Controller.
•
Check the IP addresses of other
nodes and correct the IP address
settings so that the same address is
not used by more than one node.
•
Remove the node that has the
duplicate IP address from the net-
work.
Perform allocations so that IP
addresses of nodes on the network
are used for only one node.
Attached
information
None
Precautions/
Remarks
None
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......