13-43
13 Troubleshooting
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
13-5 Even
t L
o
g
s
13
13-5-3 Error Descr
iptions
Event name
Ethernet Advanced Setting Error
Event code
34AF 0000 hex
Meaning
There is an illegal FINS setting.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON,
Controller reset,
or Unit restart
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
The relevant function stops.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power was interrupted during a
download.
Identify the cause of the error from
the detailed information in the error
history of EtherNet/IP Unit, and then
correct the settings.
Make sure that the power supply is
not interrupted during a download.
A communications error occurred dur-
ing a download.
Implement noise countermeasures if
there is excessive noise.
Implement noise countermeasures.
Attached
information
None
Precautions/
Remarks
None
Event name
Address Mismatch
Event code
34B0 0000 hex
Meaning
The host ID of the local IP address is inconsistent with the FINS node address. Or, the last segment of the local IP
address is inconsistent with the setting on the node address switches.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON,
Controller reset,
or Unit restart
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
FINS communications are not possible.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The IP address conversion method is
set to automatic generation, but the
host ID of the local IP address is
inconsistent with the FINS node
address or the last segment of the
local IP address is inconsistent with
the setting on the node address
switch.
Set the IP address or node address to
match.
None
Attached
information
None
Precautions/
Remarks
None
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......