13 Troubleshooting
13-42
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Event name
IP Router Table Error
Event code
34AD 0000 hex
Meaning
The IP router table information is incorrect.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON,
Controller reset,
or Unit restart
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
Ethernet communications for the EtherNet/IP Unit are not
possible.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power was interrupted during a
download.
Download the settings from the Sys-
mac Studio again.
Make sure that the power supply is
not interrupted during a download.
A communications error occurred dur-
ing a download.
Implement noise countermeasures if
there is excessive noise.
Implement noise countermeasures.
Attached
information
None
Precautions/
Remarks
None
Event name
Routing Table Error
Event code
34AE 0000 hex
Meaning
The routing table information is incorrect.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON,
Controller reset,
or Unit restart
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
Ethernet communications for the EtherNet/IP Unit are not
possible.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power was interrupted during a
download.
Download the settings from the Sys-
mac Studio again.
Make sure that the power supply is
not interrupted during a download.
A communications error occurred dur-
ing a download.
Implement noise countermeasures if
there is excessive noise.
Implement noise countermeasures.
Attached
information
None
Precautions/
Remarks
None
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......