13 Troubleshooting
13-30
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
* If a memory error occurs in the error log area of the non-volatile memory, the record will not be stored in the non-volatile
memory.
03D1
Ethernet advanced setting error
02 hex: FINS setting error
01 hex: Checksum error
10 hex: Invalid IP router
table
11 hex: Invalid FINS/UDP
setting
12 hex: Invalid FINS/TCP
setting
13 hex: Invalid FTP setting
14 hex: Invalid SNTP set-
ting
15 hex: Invalid SNMP set-
ting
16 hex: Invalid SNMP trap
setting
Yes
03D2
Packet discarded.
01 hex
00 hex
No
03D3
Link OFF error
00 hex
00 hex
No
03D4
Verification error (Tag data link only)
Note
For details on identifying the cause
of the verification error, refer to 13-
3 Connection Status Codes and
Error Processing.
This error will not be stored when a
target node is missing.
Connection instance num-
ber (0 to 255)
Lower eight bits of IP
address
No
03D5
Tag data link error
00 hex
Lower eight bits of IP
address
No
0601
CPU Bus Unit error
Variable
Yes
0602
CPU Bus Unit memory error
01: Read error
02: Write error
02 hex: Network parame-
ter
06 hex: Error log
09 hex: Identity data
0E hex: Unit name
0F hex: Ethernet basic
setting
10 hex: Ethernet
advanced setting
11 hex: MAC address
12 hex: Status area layout
setting
14 hex: Term Tag address
resolution memory write
error
Yes *
Error
code
(hex)
Error
Detail code
Saved in
non-volatile
memory
First byte
Second byte
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......