13 Troubleshooting
13-10
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
13-2 Using the LED Indicators and Display
for Troubleshooting
* The 7-segment display alternates between the node address and error code.
13-2-1 Errors Occurring at the EtherNet/IP Unit
Indicator
Error
Cause
Unit operation
Error log
(hex)
Countermeasure
MS
NS
7-seg-
ment*
Errors Related to CPU Unit Data Exchange
Flash-
ing red
Not lit
H1
Duplicate unit
number
The same unit num-
ber is set on another
Unit.
Operation stops.
---
Set the unit numbers
correctly and restart
the EtherNet/IP Unit.
Flash-
ing red
Not lit
H2
CPU Unit faulty
---
Operation stops.
---
Replace the CPU
Unit if the error recurs
when the CPU Unit is
restarted.
Lit red
Not lit
H3
EtherNet/IP Unit
faulty
---
Operation stops.
---
Replace the Ether-
Net/IP Unit if the error
recurs when the Unit
is restarted.
Flash-
ing red
Not lit
H4
Node address
setting error
The node address set
on the switches is
invalid (00 or FF.)
Operation stops.
---
Set the node address
correctly and restart
the EtherNet/IP Unit.
Flash-
ing red
Not lit
H6
CPU Unit faulty
---
Records the error in the
error log (time/date all
zeroes).
Operation stops.
000F
Replace the CPU
Unit if the error recurs
when the CPU Unit is
restarted.
Flash-
ing red
Not lit
H7
I/O table not reg-
istered
The CPU Unit's I/O
table is not regis-
tered.
Operation stops.
0006
Create the I/O table.
Flash-
ing red
---
H8
Restoring simple
backup data
failed.
Restoring simple
backup data failed for
some reason.
All settings for the Ether-
Net/IP Unit or built-in port
will be cleared except for
the following errors: File
missing, memory not
mounted, or inconsistent
models.
---
If the problem per-
sists even when you
repeat the simple
backup procedure,
replace the SD Mem-
ory Card, the Ether-
Net/IP Unit, or, if the
problem is with the
built-in port, the CPU
Unit.
Flash-
ing red
---
H9
I/O bus error
An error occurred
while exchanging
data with the CPU
Unit.
•
If the Unit is the origina-
tor of the tag data link
connection, it stops
communications.
•
Communications will
continue for target con-
nection. If the Unit is
the target of the tag
data link connection
and the Controller sta-
tus is included in the
communications data,
the corresponding ele-
ment in the Target
Node PLC Error Flags
will change to TRUE.
000E
Check and correct
the CPU Unit's oper-
ating environment.
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......