13 Troubleshooting
13-24
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
01
031C
Error code generated in origi-
nator:
Some other error occurred.
This error does
not occur.
The originator
generates this
code when an
unsupported
response code
is returned from
the target in
reply to a con-
nection-open-
ing request.
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
08
---
Error code returned from tar-
get:
There is no Forward Open or
Large Forward Open service
in the target device.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
D0
0001
Error code generated in origi-
nator:
The connection operation is
stopped.
The connec-
tion was
stopped
because the
Tag Data Link
Stop Bit was
changed to
TRUE, or the
settings data is
being down-
loaded.
Either change
the Tag Data
Link Start Bit to
TRUE, or wait
until the set-
tings data has
been down-
loaded.
Includes Con-
troller stop
errors, Unit fail-
ure. To handle
these errors,
refer to 13-2-1
Errors Occur-
ring at the Eth-
erNet/IP Unit.
The meaning of
this error code
is defined by
each vendor, so
it depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
D0
0002
Error code generated in origi-
nator:
The connection is being
opened (opening processing
in progress).
Wait until the
opening pro-
cessing is com-
pleted.
The meaning of
this error code
is defined by
each vendor, so
it depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
2
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......