8-9
8 Message Communications
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
8-2 Using
CIP Messa
g
e Co
mm
un
icati
ons
8
8
-2
-4 Rou
te P
a
th
Communicating between EtherNet/IP Units
Example: Communicating via EtherNet/IP Units Mounted to CPU Unit 1 and CPU Unit 2
(1) CPU Unit 1 to EtherNet/IP Unit 1
•
Network type number: “#01” (Output the command via internal backplane port.)
•
Remote address:
“#11” (Unit address of EtherNet/IP Unit (Unit number: 1+10 hex))
(2) EtherNet/IP Unit 1 to EtherNet/IP Unit 2
•
Network type number: “#02” (Output the command via EtherNet/IP port.)
•
Remote address:
Specify the remote IP address.
(3) EtherNet/IP Unit 2 to CPU Unit 2
•
Network type number: “#01” (Output the command via internal backplane port.)
•
Remote address:
“#00” (unit address of CPU Unit)
Version Information
You can use the CJ1W-EIP21 EtherNet/IP Unit mounted to an NJ-series Controller with a CPU
Unit with unit version 1.01 or later and Sysmac Studio version 1.02 or higher.
EtherNet/IP port
IP address:
192.168.250.2
Backplane
port #01
Unit address
00 hex
Unit address
11 hex
Communications
port (#02)
Backplane
port #01
EtherNet/IP Unit 2
CPU Unit 2
EtherNet/IP Unit 1
CPU Unit 1
(3) Unit address of remote CPU Unit
\01\#11\02\192.168.250.2\01\#00
(2) IP address of remote EtherNet/IP Unit
(1) Unit address of Local EtherNet/IP Unit (Unit number: 1+10 hex)
Route path
(1)
(2)
:
(3)
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......