![background image](http://html1.mh-extra.com/html/omron/sysmac-cj1w-eip21/sysmac-cj1w-eip21_operation-manuals_742257406.webp)
Appendices
A-32
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
CIO n+11: Unit Status 2
The device variable that corresponds to all of the bits in CIO n+11 is given in the following table.
The device variables that correspond to bits 00 to 15 in CIO n+11 are given in the following table.
CIO n+12: Communications Status 1
The device variable that corresponds to all of the bits in CIO n+12 is given in the following table.
The device variables that correspond to bits 00 to 15 in CIO n+12 are given in the following table.
I/O memory location in CJ-
series CPU Unit
Device variable for the CJ-series Unit in NJ-series CPU Unit
Word address
Bit numbers
Variable name
Description
CIO n+11
00 to 15
*_UnitSta2
Unit Status 2
(The functions of bits 00 to 15 in CIO n+11
correspond to the functions of bits 00 to 15 of
the device variable given on the left.)
I/O memory location in CJ-
series CPU Unit
Device variable for the CJ-series Unit in NJ-series CPU Unit
Word address
Bit numbers
Variable name
Description
CIO n+11
0
*_ETNOnlineSta
Online
1
*_TDLOprSta
Tag Data Link Operating
2
*_IPAdrChgErr
Operating IP Address Change
03 to 10
---
Not used.
11
*_UserStaAreaEnblSta
User Settings Area Enabled
12 and 13
---
Not used.
14
*_MultiSwOnErr
Multiple Switches ON Error
15
*_ErrLogStoreSta
Error Log Stored
I/O memory location in CJ-
series CPU Unit
Device variable for the CJ-series Unit in NJ-series CPU Unit
Word address
Bit number
Variable name
Description
CIO n+12
00 to 15
Communications Status 1
Communications Status 1
(The functions of bits 00 to 15 in CIO n+12
correspond to the functions of bits 00 to 15 of
the device variable given on the left.)
I/O memory location in CJ-
series CPU Unit
Device variable for the CJ-series Unit in NJ-series CPU Unit
Word address
Bit number
Variable name
Description
CIO n+12
0
*_TDLOpnErr
Verification Error
1
---
Not used.
2
*_TDLErr
Tag Data Link Error
3
---
Not used.
4
*_CommParamErr
Invalid Communications Parameter
5
*_TagRefreshErr
Tag Refresh Error
6
*_TagDbErr
Tag Database Error
07 to 13
---
Not used.
14
*_TDLAllRunSta
All Tag Data Links Operating
15
*_TDLRunSta
Tag Data Links Operating
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......