13-21
13 Troubleshooting
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
13
-3 Co
nn
ectio
n Status C
ode
s and
Er
ro
r Pr
oc
essing
13
01
0107
Error code returned from tar-
get:
Attempted to close a connec-
tion, but that connection was
already closed.
This error does
not occur.
This error does
not occur.
This is not an
error because
the connection
is already
closed.
01
0108
Error code returned from tar-
get:
Attempted to open a connec-
tion with an unsupported con-
nection type.
This error does
not occur.
Check which
connection
types can be
used by the tar-
get. (Contact
the manufac-
turer.)
Only multicast
and point-to-
point can be
set.
Check which
connection
types can be
used by the
originator.
(An error will
occur if a con-
nection other
than multicast
or point-to-point
is set.)
01
0109
Error code returned from tar-
get:
The connection size settings
are different in the originator
and target.
Check the connection sizes set in the originator and
target.
01
0110
Error code returned from tar-
get:
The target was unable to
open the connection, because
of its operating status, such
as downloading settings.
Check whether
the tag data link
is stopped at
the target.
(Restart the tag
data link com-
munications
with the soft-
ware switch.)
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Check whether
the tag data link
is stopped at
the originator.
(Restart the tag
data link com-
munications
with the soft-
ware switch.)
01
0111
Error code returned from tar-
get:
The RPI was set to a value
that exceeds the specifica-
tions.
This error does
not occur.
Check the tar-
get’s RPI set-
ting
specifications.
Set the origina-
tor’s RPI setting
to 10 seconds
or less.
01
0113
Error code generated by origi-
nator or returned from target:
Attempted to open more con-
nections than allowed by the
specifications (CJ2M-EIP21:
32, other CPU Units: 256).
Check the con-
nection set-
tings (number
of connec-
tions) at the
originator and
target.
Check the con-
nection set-
tings (number
of connec-
tions) at the
originator and
target.
Check the con-
nection specifi-
cations for
another com-
pany’s devices.
Check the con-
nection set-
tings (number
of connec-
tions) at the
originator and
target.
Check the con-
nection specifi-
cations for
another com-
pany’s devices.
01
0114
Error code returned from tar-
get:
The Vendor ID and Product
Code did not match when
opening connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Confirm that
the target
device’s EDS
file is correct.
Check the origi-
nator’s connec-
tion settings.
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
2
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......