13 Troubleshooting
13-12
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
* The 7-segment display alternates between the node address and error code.
Indicator
Error
Cause
Unit operation
Error log
(hex)
Countermeasure
MS
NS
7-seg-
ment*
Errors Related to CPU Unit Data Exchange
Flash-
ing red
---
HE
CPU Unit service
monitoring error
Servicing from the
CPU Unit was not
completed within the
fixed interval. The
monitoring time is
normally 11 s.
•
If the Unit is the origina-
tor of the tag data link
connection, it stops
communications.
•
Communications will
continue for target con-
nection. If the Unit is
the target of the tag
data link connection
and the Controller sta-
tus is included in the
communications data,
the corresponding ele-
ment in the Target
Node PLC Error Flags
will change to TRUE.
Note
Recovery is possi-
ble for this error.
When operation is
restored, tag data
link startup pro-
cessing will be per-
formed and
operations will
return to normal.
0002
Check and correct
the CPU Unit's oper-
ating environment.
Flash-
ing red
---
HF
CPU Unit watch-
dog timer error
An error occurred in
the CPU Unit.
•
If the Unit is the origina-
tor of the tag data link
connection, it stops
communications.
•
Communications will
continue for target con-
nection. If the Unit is
the target of the tag
data link connection
and the Controller sta-
tus is included in the
communications data,
the Target Node PLC
Error Flags will change
to TRUE.
0001
Replace the CPU
Unit.
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......