13 Troubleshooting
13-44
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Event name
Status Area Layout Setting Error
Event code
381C 0000 hex
Meaning
An error occurred in the layout setting of the EtherNet/IP Unit.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON,
Controller reset,
or Unit restart
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
Operation will be performed with the default layout set-
tings while this error exists. In the following case, however,
operation is performed with the user-set layout settings.
•
A non-existent area is specified.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
There is an error in the layout settings
of the EtherNet/IP Unit.
Correct the layout settings of the Eth-
erNet/IP Unit.
Check that there are no errors in the
layout settings of the EtherNet/IP
Unit.
Attached
information
None
Precautions/
Remarks
None
Event name
Multiple Switches ON Error
Event code
54AE 0000 hex
Meaning
More than one software switch changed to TRUE at the same time.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At software
switch operation
Error attributes
Level
Minor fault
Recovery
Automatic recov-
ery
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
More than one software switch
changed to TRUE at the same time.
Or, another software switch changed
to TRUE before processing was com-
pleted for a previous software switch.
Do not allow more than one software
switch to be TRUE at the same time.
Do not allow more than one software
switch to be TRUE at the same time.
Attached
information
None
Precautions/
Remarks
You can change the event level to the observation level. If you change the level to the observation level, recovery proce-
dures are not required.
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......